3-21. Installing the Drain Piping

(1) Prepare standard hard PVC pipe (O.D. 1-1/4") for the

drain and use the supplied drain socket to prevent water
leaks. The PVC pipe must be purchased separately.
When doing this, apply adhesive for the PVC pipe at the
connection point.

(2) If connecting a drain joint (supplied) to the threaded

drain port, first wrap the drain port threads with sealing
tape, then connect the joint. (Fig. 3-83)

(3) After connecting the drain pipe securely, wrap insulator

(field supply) around the pipe.

(4) Ensure the drain pipe has a downward gradient (1/100

or more) and prepare traps as indicated in Fig. 3-84.

(5) Also, in another part of the pipe arrangement, prepare

traps with an inspection plug to clean dust or debris that
may cause leaking of water. (Fig. 3-85)

(6) After connecting the drain piping, slowly pour water into

the drain pan to check that the water drains smoothly.

3-22. Caution for Ducting Work

This unit has high static pressure (applicable external static
pressure Max. 0.68 – 0.88 in.WG. In the case of small
pressure resistance (for instance, a short duct), install a
damper for adjusting air flow volume as air flow volume /
air flow noise increases.

If the air conditioner is to be installed in a room such as
an office or meeting room which needs a low sound
level, provide a supply and return noise absorption
chamber with an acoustic liner.

Include an air filter (field supply) at the return duct.

3-23. Indoor Fan Performance

How to Read the Diagram

The vertical axis is the External Static Pressure
(in.WG) while the horizontal axis represents the
Air Flow (CFM). The characteristic curve for the
“H,” “Med,” and “Lo” fan speed control.
The nameplate values are shown based on the
“H” air flow. Therefore in the case of 36 Type,
the flow is 1059 CFM, while the External Static
Pressure is 0.72 in.WG at “H” position. If the
external static pressure is too great (due to long
extension of duct, for example), the air flow
volume may drop too low at each air outlet.

Sealing tape

Drain joint
(supplied)

Drain pan

Drain opening
(25A or 1-11/32" male screw)

Limit li

ne

Lim

it li

ne

H

H

M

M

L

883

1059

1236

Air Flow (CFM)

Air Flow (CFM)

Limi

t lin

e

Limit li

ne

H

H,M

M

L

1059

1236

1412

36 Type

48 Type

H: At shipment

NOTE

Exter

n

al

S

tatic Pre

ssu

re

0.20

0

0.40

0.60

0.80

1.00

(in.WG)

Exter

n

al

S

tatic Pre

ssu

re

0.20

0

0.40

0.60

0.80

1.00

(in.WG)

Fig. 3-86