Sanyo AHX0952 User Manual

Page 13

Advertising
background image

WARNING

Always check the gas density
limit for the room in which the
unit is installed.

1-10. Check of Limit Density

When installing an air conditioner in a room, it is neces-

sary to ensure that even if the refrigerant gas accidentally

leaks out, its density does not exceed the limit level for

that room.

If the density could exceed the limit level, it is necessary to

provide an opening between the unit and the adjacent

room, or to install mechanical ventilation which is inter-

locked with the leak detector.

(Total refrigerant charged amount: oz)

(Min. indoor volume where the indoor unit is installed: ft.

3

)

< Limit density 0.3 (oz/ft.

3

)

The limit density of refrigerant which is used in this unit is
0.3 oz/ft.

3

(ISO 5149).

The shipped outdoor unit comes charged with the amount

of refrigerant fixed for each type, so add it to the amount

that is charged in the field. (For the refrigerant charge

amount at shipment, refer to the unit’s nameplate.)

1-11. Installing Distribution Joint

(1) Refer to “HOW TO ATTACH DISTRIBUTION JOINT”

enclosed with the optional distribution joint kit

(APR-P160BA).

(2) In order to prevent accumulation of refrigerant oil in

stopped units, if the main tubing is horizontal then each

branch tubing length should be at an angle that is

greater than horizontal. If the main tubing is vertical,

provide a raised starting portion for each branch.

(3) If there are height differences between indoor units or if

branch tubing that follows a distribution joint is connect-

ed to only 1 unit, a trap or ball valve must be added to

that distribution joint. (When adding the ball valve,

locate it within 1.3 ft. of the distribution joint.)

(Consult with SANYO separately concerning the ball

valve.)

If a trap or ball valve is not added, do not operate

the system before repairs to a malfunctioning unit

are completed. (The refrigerant oil sent through the

tubing to the malfunctioning unit will accumulate

and may damage the compressor.)

Minimum indoor volume & floor area as against the
amount of refrigerant is roughly as given in the following
table.

0

0

57

114

170

227

284

341

398

454

511

568

625

682

738

795

852

909

966

1022

1079

1136

0

500

1000

1500

2000

2500

3000

3500

4000

4500

5000

5500

6000

6500

7000

7500

8000

8500

9000

9500

10000

1000

500

1500 2000 2500 3000

Total amount of refrigerant

Mi

n

. i

n

door v

o

lu

me

Mi

n

. i

n

door floor area

(whe

n

the ceili

ng

i

s

8

.8

ft.

hi

g

h)

ft.

3

ft.

2

oz

Range above
the density limit of
0.3 oz/ft.

3

(countermeasures
needed)

Range below
the density limit of
0.3 oz/ft.

3

(countermeasures
not needed)

15 to 30

°

B

A

B

A

Tube branching methods (horizontal use)

Arrow view

Horizontal
line

View as seen
from arrow

Types of vertical trap specifications

(When using ball valve)

Main tubing

Ball valve

(BV: purchased

separately)

Indoor unit (1)

Indoor unit (more than 2 units)
(If only 1 unit is connected,
a ball valve is also needed on this side.)

(When not using ball valve)

Main tubing

Indoor unit is directed downward

More than
8 in.

Horizontal

Indoor unit

(Each unit is connected to
tubing that is either level
or is directed downward.)

Branch tubing is
directed upward.

CAUTION

Pay special attention to any
location, such as a basement,
etc., where leaking refrigerant
can accumulate, since refrig-
erant gas is heavier than air.

13

07-056 Mini_ECOi_II_NA 3/19/07 2:40 PM Page 13

Advertising