Checking the indoor unit addresses

Use the remote controller to check the indoor unit address.

<If 1 indoor unit is connected to 1 remote controller>

1. Press and hold the

button and

button for 4 seconds or longer (simple settings mode).

2. The address is displayed for the indoor unit that is connected to the remote controller.

(Only the address of the indoor unit that is connected to the remote controller can be checked.)

3. Press the

button again to return to normal remote controller mode.

<If multiple indoor units are connected to 1 remote controller (group control)>

1. Press and hold the

button and

button for 4 seconds or longer (simple settings mode).

2. “ALL” is displayed on the remote controller.

3. Next, press the

button.

4. The address is displayed for 1 of the indoor units which is connected to the remote controller. Check that the fan

of that indoor unit starts and that air is discharged.

5. Press the

button again and check the address of each indoor unit in sequence.

6. Press the

button again to return to normal remote controller mode.

Remote Controller Test Run Settings

1. Press the remote controller

button for 4 seconds or longer. Then press the

button.

“TEST” appears on the LCD display while the test run is in progress.

The temperature cannot be adjusted when in Test Run mode.
(This mode places a heavy load on the machines. Therefore use it only when performing the test run.)

2. The test run can be performed using the HEAT, COOL, or FAN operation modes.

Note: The outdoor units will not operate for approximately 3 minutes after the power is turned ON and after

operation is stopped.

3. If correct operation is not possible, a code is displayed on the remote controller display.

(Refer to “7-6. Meaning of Alarm Messages” and correct the problem.)

4. After the test run is completed, press the

button again. Check that “TEST” disappears from the remote con-

troller display.

(To prevent continuous test runs, this remote controller includes a timer function that cancels the test run after

60 minutes.)

* If the test run is performed using the wired remote controller, operation is possible even if the cassette-type ceil-

ing panel has not been installed. (“P09” display does not occur.)

Number changes to indicate which indoor unit is currently selected.