1-9. Tubing Length

Table 1-16 Ranges that Apply to Refrigerant Tubing Lengths and to Differences in Installation Heights

R410A distribution joint
APR-P160BA (for indoor unit)

Note: Do not use commercially available T-joints for the liquid tubing.

H2

LD

L1
L2

LC

LB

LA

* Be sure to use special R410A distribution joints (APR: purchased separately) for outdoor
unit connections and tubing branches.

Main tube of unit

1st branch

Unit distribution tube

1

2

3

n-1

n

L3

H1

Items

Marks

Contents

Length (ft.)

L1

Max. tubing length

Actual length

492

Equivalent length

574

L (L2 – L3)

Difference between max. length and min.

131

length from the No.1 distribution joint

1

,

2

...

n

Max. length of each distribution tube

98

1

+

2

+...

n–1

Total max. tubing length including length of

656

each distribution tube (only narrow tubing)

H1

When outdoor unit is installed higher than indoor unit

164

When outdoor unit is installed lower than indoor unit

131

H2

Max. difference between indoor units

49

L = Length, H = Height

Allowable tubing
length

>

>

Allowable elevation
difference

>

>

>

>

>

>

+L1

Select the installation location so that the length and size of refrigerant tubing are within the allowable range shown
in the figure below.

07-056 Mini_ECOi_II_NA 3/19/07 2:40 PM Page 12