Service Manual 47

Operation

Function of Outdoor Unit

Outdoor Unit

Two Comp algorithm

Operating Step

LEV Control

Out door Fan Control

• Compressor step varies considering condition such as room temp,outdoor temp, operating room

number,Temp gap between room temp and set temp and so on.

• LEV pulse is modulated to keep constant superheat or subcooling.

• Outdoor fan operates at High or Off to respond to the load condition.

R/Valve Control(Heating Model Only)

• Convert R/Valve to change cooling to heating, heating to cooling.

Defrost Function

• After 45 min heating operation, check the defrost condition and if outdoor pipe temp is below -

5

°

C(23

°

F) and released from deice operation in case outdoor pipe temp is over 12

°

C(53.6

°

F) or 9 min

cooing mode.

• To deice outdoor heat exchanger in low temp condtion, convert operating mode from heating to

Oil Return System

• In single(one) comp operation duration, another comp will operate for 30 seconds every 1 hours.

Comp Overload Protection

• To protect comp from being overload, protector will turn off the comp.

High Pressure Protction

• If cycle pressure is too high(around 36.7 kgf/cm

2

), it will turn off comp A

• Inverter Comp is first priority and then Constant Comp is turning on responding to load condtion.