74 Multi type Air Conditioner

Troubleshooting Guide

Error

Title

Cause of error

Check point & Normal condition

code

33

D-Pipe Temp. High

• Discharge sensor

temp. high

• Check the discharge pipe sensor.
• Check the install condition for over load.
• Check the leakage of refrigerent.
• Check the SVC V/V open.

Error

Title

Cause of error

Check point & Normal condition

code

51

Capacitor error

• Over Capacitor com-

bination

• Check the indoor unit capacity.
• Check the combination table

Check Point

1. Check the indoor unit capacity.

2. Check the combination table.

In the tropical model case

single cycle has no error for over capacity.

Check Point

1. Check the install condition for over load.

2. Check the SVC V/V open.

3. Check the leakage of refrigerent.

4. Check the constant compressor.

COMP OFF

LEV OPEN(16PULSE/MIN)

LEV OPEN(10PULSE/MIN)

NORMAL

A3UH363FA0(LMU360HE)/A3UC363FA0(LMU360CE)

115

°

C(239

°

F)

100

°

C(212

°

F)

95

°

C(203

°

F)