Service Manual 75

Troubleshooting Guide

Error

Title

Cause of error

Check point & Normal condition

code

44

Outdoor air sensor

45

Condensor pipe sensor

47

D-Pipe sensor

• Open / Short
• Soldered poorly
• Internal circuit error

• Open / Short
• Soldered poorly
• Internal circuit error

• Open / Short
• Soldered poorly
• Internal circuit error

Normal resistor : 10K

/ at 25°C(77°F) (Unplugged)

Normal voltage : 2.5Vdc / at 25°C(77°F) (plugged)

Normal resistor : 5K

/ at 25°C(77°F) (Unplugged)

Normal voltage : 2.5Vdc / at 25°C(77°F) (plugged)

Normal resistor : 200K

/ at 25°C(77°F) (Unplugged)

Normal voltage : 4.5Vdc / at 25°C(77°F) (plugged)

Check Point

1. Estimate the resistance of each sensor.(Unplugged)

2. Estimate the voltage of each sensor.(Plugged)

3. If the resistance is 0V or 5Vdc, then sensor is abnormal

Check the resistance