Self-diagnosis function, Indoor error outdoor error – LG A3UH363FA0 User Manual

Page 65

Advertising
background image

Service Manual 65

Troubleshooting Guide

Error Indicator

• The function is to self-diagnoisis airconditioner and express the troubles identifically if there is any trouble.
• Error mark is ON/OFF for the operation LED of evaporator body in the same manner as the following table.
• If more than two troubles occur simultaneously, primarily the highest trouble fo error code is expressed.
• After error occurrence, if error is released, error LED is also released simultaneously.
• To operate again on the occurrence of error code, be sure to turn off the power and then turn on.
• Having or not of error code is different from Model.

Self-diagnosis Function

00

No Error

ON

01

Indoor Room Thermistor Error

1 time

OFF

02

Indoor In-Piping Error

2 times

OFF

05

Communication Error between In and Out

5 times

OFF

06

Indoor Out-Piping Error

6 times

OFF

07

Differnt mode operation

7 times

OFF

10

Indoor fan motor locked error

1 times

OFF

Error code

Description

MPS Variable

LED1

LED2

Indoor Status

33

D-Pipe High(Normal)

3 times

3 times

OFF

44

Outdoor Air Thermistor Error(Open/Short)

4 times

4 times

OFF

45

Cond Pipe Thermistor Error(Open/Short)

4 times

5 times

OFF

47

Const. D-Pipe Thermistor Error(Open/Short)

4 times

7 times

OFF

51

Capcity Error(High/Low)

5 times

1 times

OFF

Error code

Description

MPS Variable

LED1(Red)

LED2(Green) Indoor Status

Indoor Error

Outdoor Error

LED1