Way, 3-way valve – LG A3UH363FA0 User Manual

Page 76

Advertising
background image

76 Multi type Air Conditioner

2-way, 3-way Valve

2-way, 3-way Valve

2-way Valve (Liguid Side)

3-way Valve (Gas Side)

Works

Shaft position

Shaft position

Service port

Shipping

Closed

Closed

Closed

(with valve cap)

(with valve cap)

(with cap)

Air purging

Open

Closed

Open

(Installation)

(counter-clockwise)

(clockwise)

(push-pin or with

vacuum pump)

Operation

Open

Open

Closed

(with valve cap)

(with valve cap)

(with cap)

Pumping down

Closed

Open

Open

(Transfering)

(clockwise)

(counter-clockwise)

(connected

manifold gauge)

Evacuation

Open

Open

Open

(Servicing)

(with charging

cylinder)

Gas charging

Open

Open

Open

(Servicing)

(with charging

cylinder)

Pressure check

Open

Open

Open

(Servicing)

(with charging

cylinder)

Gas releasing

Open

Open

Open

(Servicing)

(with charging

cylinder)

3.

2.

1.

4.

5.

6.

Flare nut

To

piping

connection

Open position
Closed position

Flare nut

Valve cap

To

piping

connection

Open position
Closed position

Hexagonal wrench
(4mm)

To outdoor unit

Pin

Service
port

Service
port cap

To outdoor unit

Advertising
This manual is related to the following products: