72 Multi type Air Conditioner

Troubleshooting Guide

Error Code

Trouble Shooting

Error

Title

Cause of error

Check point & Normal condition

code

01

Indoor air sensor

02

Indoor inlet pipe sensor

06

Indoor outlet pipe sensor

• Open / Short
• Soldered poorly
• Internal circuit error

• Open / Short
• Soldered poorly
• Internal circuit error

• Open / Short
• Soldered poorly
• Internal circuit error

Normal resistor : 10K

/ at 25°C (Unplugged)

Normal voltage : 2.5Vdc / at 25°C (plugged)

Normal resistor : 5K

/ at 25°C (Unplugged)

Normal voltage : 2.5Vdc / at 25°C (plugged)

Normal resistor : 5K

/ at 25°C (Unplugged)

Normal voltage : 2.5Vdc / at 25°C (plugged)

10K

2.5Vdc

Check the resistance / voltage

V

Check Point

1. Unplug the sensor on Indoor unit PCB.

2. Estimate the resistance of each sensor

3. If the resistance of the sensor is 10K

/5K

at 25°C, then sensor is normal

4. If the resistance of the sensor is 0 K

or

, then sensor is abnormal.

Change the sensor.

5. Plug the sensor on Indoor unit PCB and Power ON.

6. Estimate the voltage of each sensor.

7. If the voltage of the sensor is 2.5Vdc / at 25°C, then sensor is normal.

8. If the resistance of the sensor is 0 or 5Vdc, then sensor is abnormal.

Repair or Change the PCB