172 Aries User Guide

Over-Voltage Protection

The Aries drive’s over-voltage circuit protects the drive from excessive
regeneration. If the voltage on the motor output terminals rises above the
threshold voltage, the drive issues an over-voltage fault and turns off power
to the motor output terminals (Motor connector). This allows the motor to
freewheel to a stop.

Threshold Voltage
All Models................................................ 410 VDC

Results of Fault ....................................... Power to motor is turned OFF

Fault output is activated

LED Left

LED Right

Yellow
& 4 Green (blinking)

Red

Table

56

LED

Over-Voltage

Fault

Resetting the fault

To clear the latched fault, choose one of the following methods:

Cycle power to the Aries drive.

–or–

► Open the Aries Support Tool. Then select Operating System Update

from the menu and click Reset Drive.

Warning —

Over-voltage protection monitors only the motor output terminals

(DC motor bus). It does not protect against an over voltage on the AC input
terminals, which can permanently damage the drive.

Warning —

When an over-voltage protection fault occurs, the drive disables

power to its motor output terminals on the Motor connector. This cuts all
control to the motor and allows the load to freewheel.