Chapter 3 Electrical Installation 41

Warning —

You must connect the drive’s protective conductor terminal, marked

with the earth symbol

, to a reliable system Protective Earth.

Warning —

The drive’s connector strip terminals have hazardous voltages when

power is applied to the drive, and up to several minutes after power is removed.
Lower voltages may still be present for several minutes after power is removed.
During normal operation, these high voltage terminals must not be accessible to
the user.

Motor Power Fuse Information

Aries drives have no user-serviceable internal fuses. For safety, you must
provide a fuse in each of the AC Mains Motor power input lines. To
determine the proper fuse type and size for your application, see Table 14.
(For fuse recommendations for Control-power input lines, see “Control Power
Supply” on page

46

.)

Drive

AC Voltage

Fuse Style

Rating

Fuse Type

120 VAC

125 VAC Time Delay 10A

RK5 or better

AR-01xx

240 VAC

250 VAC Time Delay 10A

RK5 or better

120 VAC

125 VAC Time Delay 10A

RK5 or better

AR-02xx

240 VAC

250 VAC Time Delay 10A

RK5 or better

120 VAC

125 VAC Time Delay 20A

RK5 or better

AR-04xx

240 VAC

250 VAC Time Delay 20A

RK5 or better

120 VAC

125 VAC Time Delay 20A

RK5 or better

AR-08xx

240 VAC

250 VAC Time Delay 20A

RK5 or better

120 VAC

125 VAC Time Delay 30A

RK5 or better

AR-13xx

240 VAC

250 VAC Time Delay 30A

RK5 or better

AR-20xE*

240 VAC

250 VAC Time Delay 40A

RK5 or better

AR-30xE*

240 VAC

250 VAC Time Delay 40A

RK5 or better

*

The 40A fuse is recommended regardless of whether the input power is
single-phase or 3-phase.

Table 14 Motor Power Fuse Information