IOLAN SDS/SCS/STS/MDC User’s Guide, Version 4.0

Field Descriptions

Configure the following parameters:

Description

Type

Range

Alarm Settings
Button

s

See

Alarm Settings on page 271

for field descriptions.

Provide a description of the channel, making it easier to identify.

Data Options: Maximum 20 characters, including spaces

Specify the type of sensor you are using to measure temperature.

Data Options: RTD, Thermocouple

Default: RTD

Specify the temperature range that you want to measure.

Data Options:

z

RTD—Pt100 a=385 -50 to 150C, Pt100 a=385 0 to 100C,

Pt100 a=385 0 to 200C, Pt100 a=385 0 to 400C,

Pt100 a=385 -200 to 200C, Pt100 a=392 -50 to 150C,

Pt100 a=392 0 to 100C, Pt100 a=392 0 to 200C,

Pt100 a=392 0 to 400C, Pt100 a=392 -200 to 200C,

Pt1000 a=385 -40 to 160C, NiFe604 a=518 -80 to 100C,

NiFe604 a=518 0 to 100C

z

Thermocouple—B 500 to 1800C, E 0 to 1000C,

J 0 to 760C, K 0 to 1370C, R 500 to 1750C,

S 500 to 1750C, T -100 to 400C

Default: RTD is Pt100 a=385 -50 to 150C. Thermocouple is J 0 to 760C.

Click the

Alarm Settings

button to specify the trigger and clear levels for the

alarms. Notice that the Analog Alarm Settings window has two alarm
configuration views, a basic alarm view and an advanced alarm view.