National Instruments NI PXIe-1075 User Manual

Page 19

Advertising
background image

Chapter 1

Getting Started

NI PXIe-1075 User Manual

1-12

ni.com

To synchronize the system to an external clock, you can drive PXI_CLK10
from an external source through the PXI_CLK10_IN pin on the System
Timing Slot. Refer to Table B-5,

XP4 Connector Pinout for the System

Timing Slot

, for the pinout. When a 10MHz clock is detected on this pin,

the backplane automatically phase-locks the PXI_CLK10, PXIe_CLK100,
and PXIe_SYNC100 signals to this external clock and distributes these
signals to the slots. Refer to Appendix A,

Specifications

, for the

specification information for an external clock provided on the
PXI_CLK10_IN pin of the system timing slot.

You also can drive a 10MHz clock on the 10 MHz REF IN connector on
the rear of the chassis. Refer to Figure 1-2 for the location of this connector.
When a 10MHz clock is detected on this connector, the backplane
automatically phase-locks the PXI_CLK10, PXIe_CLK100, and
PXIe_SYNC100 signals to this external clock and distributes these signals
to the slots. Refer to Appendix A,

Specifications

, for the specification

information for an external clock provided on the 10 MHz REF IN
connector on the rear panel of the chassis.

If the 10 MHz clock is present on both the PXI_CLK10_IN pin of the
System Timing Slot and the 10 MHz REF IN connector on the rear of the
chassis, the signal on the System Timing Slot is selected. Refer to Table 1-3
which explains how the 10 MHz clocks are selected by the backplane.

Table 1-3. Backplane External Clock Input Truth Table

System Timing Slot

PXI_CLK10_IN

Rear Chassis Panel

10 MHz REF IN

Backplane PXI_CLK10,

PXIe_CLK100 and PXIe_SYNC100

No clock present

No clock present

Backplane generates its own clocks

No clock present

10 MHz clock present

PXI_CLK10, PXIe_CLK100 and
PXIe_SYNC100 all phase-locked to
Rear Chassis Panel—10 MHz REF IN

10 MHz clock present

No clock present

PXI_CLK10, PXIe_CLK100 and
PXIe_SYNC100 all phase-locked to
System Timing Slot— PXI_CLK10_IN

10 MHz clock present

10 MHz clock present

PXI_CLK10, PXIe_CLK100 and
PXIe_SYNC100 all phase-locked to
System Timing Slot—PXI_CLK10__IN

Advertising