Chapter 8 pfi, Figure 8-1. ni 6238/6239 pfi input circuitry – National Instruments NI 6238 User Manual

Page 106

Advertising
background image

© National Instruments Corporation

8-1

NI 6238/6239 User Manual

8

PFI

NI 6238/6239 devices have 10 Programmable Function Interface (PFI)
signals—six input signals and four output signals.

Each PFI <0..5>/P0.<0..5> can be configured as a timing input signal for
AI or counter/timer functions or a static digital input. Each PFI input also
has a programmable debouncing filter.

Caution When making measurements, take into account the minimum pulse width and
time delay of the digital input and output lines.

Figure 8-1 shows the circuitry of one PFI input line. Each PFI line is
similar.

Figure 8-1. NI 6238/6239 PFI Input Circuitry

Each PFI <6..9>/P1.<0..3> can be configured as a timing output signal
from AI, AO, or counter/timer functions or a static digital output.

Figure 8-2 shows the circuitry of one PFI output line. Each PFI line is
similar.

To Input Timing
Signal Selectors

Isolation

Barrier

Digital

Isolators

PFI <0..5>/P0.<0..5>

PFI

Filters

Static DI