FPI P36D-1 Zero Clearance Direct Vent Gas Fireplace

27

The P36D-1 is approved for a 40 ft. straight vertical,
with rigid pipe vent systems for Propane and Natural
Gas, as per the diagram 1.

The shaded area in the diagram 1 shows all
allowable combinations of straight vertical and
offset to vertical terminations with rigid pipe vent
systems for Propane and Natural Gas. Maximum
two 45

o

elbows allowed.

• Vent must be supported at offsets

• Firestops are required at each fl oor level

and whenever passing through a wall.

• Maintain clearances to combustibles.

Diagram 1

INSTALLATION