FPI P36D-1 Zero Clearance Direct Vent Gas Fireplace

29

V

H1

H

V1

INSTALLATION

VERTICAL VENTING WITH TWO (2) 90

O

ELBOWS

VERTICAL VENTING WITH THREE (3) 90

O

ELBOWS

V1

V

H

Option V

H

V + V1

A)

0' Min. 2' Max. 1' Min.

B)

1' Min. 4' Max. 3' Min.

C)

2' Min. 5' Max. 4' Min.

D)

3' Min. 6' Max. 5' Min.

E)

4' Min. 7' Max. 6' Min.

F)

5' Min. 8' Max. 7' Min.

With these options, max. total
pipe length is 30 feet with min.
of 7 feet total vertical and max.
8 feet total horizontal.

Please note min. 1 foot
between 90

o

elbows is

required.

One 90

o

elbow = Two 45

o

elbows.

Lengths do not include elbow indicated.

Option V

H + H1 V + V1

A)

0' Min. 2' Max. 2' Min.

B)

1' Min. 2' Max. 3' Min.

C)

2' Min. 3' Max. 4' Min.

D)

3' Min. 4' Max. 6' Min.

E)

4' Min. 5' Max. 7' Min.

F)

5' Min. 6' Max. 8' Min.

G)

6' Min. 7' Max. 9' Min.

H)

7' Min. 8' Max. 10' Min.

With these options, max.
total pipe length is 30 feet
with min. of 10 feet total
vertical and max. 8 feet
total horizontal.

Please note min. 1 foot
between 90

o

elbows is

required.

One 90

o

elbow = Two 45

o

elbows.

Lengths do not include elbow indicated.