Mobile home, Caution, Warning – Quadra-Fire CASTILE-CCR User Manual

Page 16

Advertising
background image

Page 16

250-6422D

October 11, 2005

R

Castile Pellet Stove

RR

6

Mobile Home

1. An outside air inlet must be provided for the combustion

air and must remain clear of leaves, debris, ice and/or

snow. It must be unrestricted while the appliance is

in use to prevent room air starvation which causes

smoke spillage. Smoke spillage can also set off smoke

alarms.

2. The combustion air duct system must be made of

metal. It must permit zero clearance to combustible

construction and prevent material from dropping into

the inlet or into the area beneath the dwelling and

contain a rodent screen.

3. The appliance must be secured to the mobile home

structure by bolting it to the floor (using lag bolts).

Use the same holes that secured the appliance to the

shipping pallet.

4. The appliance must be grounded with #8 solid copper

grounding wire or equivalent, terminated at each end

with an NEC approved grounding device.

5. Refer to clearances to combustibles and floor protection

requirements on

pages 8 & 9 for listings to combus-

tibles and appropriate chimney systems.

6. Use silicone to create an effective vapor barrier at

the location where the chimney or other component

penetrates to the the exterior of the structure.

7. Follow the chimney manufacturer’s instructions when

installing the vent system for use in a mobile home.

8. Installation shall be in accordance with the Manufactur-

ers Home & Safety Standard (HUD) CFR 3280, Part

24.

CAUTION

Maintain structural integrity of mobile home:

• Floor, wall, ceiling and/or roof.

Do NOT cut through:

• Floor joist, wall, studs or ceiling trusses.

• Any supporting material that would affect the structural

integrity.

Never install in a sleeping room.

WARNING

Installation must comply with Manufactured Home and

Safety Standard (HUD), CFR 3280, Part 24.

WARNING

You must use a Quadra-Fire Outside Air Kit

for installation in a mobile home.

A. Mobile Home Installation

Spark Arrestor Cap

Roof Flashing

Storm Collar

Joist Shield/Firestop

Double Wall

Pellet Vent

Figure 16.1

CAUTION

Never draw outside combustion air from:

• Wall, floor or ceiling cavity

• Enclosed space such as an attic or garage

Advertising
This manual is related to the following products: