H. prefabricated metal chimney – Quadra-Fire PELLET INSERT CB1200MI-MBK User Manual

Page 11

Advertising
background image

R

R

R

February 3, 2010

7014-188B

Page 11

CB1200-I Pellet Insert

G. Calculating Alternate Floor Protection Material

Thermal Conductivity: k value
The k value indicates the amount of heat (in BTU’s) that will flow

in 1 hour through 1 square foot of a uniform material 1 inch thick

for each degree (F) of temperature difference from one side of

the material to the other. The LOWER the k factor means less

heat is being conducted through the non-combustible material to

the combustible material beneath it. The k value of a material

must be equal or smaller then the required k value to be accept-

able.

(BTU) (inch)

(foot

2

(hour) (

o

F)

Thermal Resistance: R value
The R value is a measure of a material’s resistance to heat

transfer. R value is convenient when more than one materi-

al is used since you can add the R values together, whereas

you can not do this for k value. The HIGHER the R factor

means less heat is being conducted through the non-com-

bustible material to the combustible material beneath it. The

R value of a material must be equal or larger then the re-

quired R value to be acceptable.
Converting k to R:
Divide 1 by k and multiply the results times the thickness in inch-

es of the material.

R = 1/k x inches of thickness

Converting R to k:
Divide the inches of thickness by R.

k = inches of thickness/R

Calculations:
Example: Floor protection requires k value of 0.84 and 3/4 inch

thick.
Alternative material has a k value of 0.6 and is 3/4 inch thick.
Divide 0.6 by .75 = k value of 0.80. This k value is smaller than

0.84 and therefore is acceptable.

H. Prefabricated Metal Chimney

The chimney can be new or existing, masonry or prefabricated

and must meet the following minimum requirements:
• Must be minimum 6 inch (152mm) inside diameter of

high temperature chimney listed to UL 103 HT (2100

o

F)

or ULC-S628.

• Must use components required by the manufacturer for

installation.

• Must maintain clearances required by the manufacturer

for installation.

• Refer to manufacturers instructions for installation
•This insert is listed to UL 1482 Standard and is approved

for installation into listed factory-built zero clearance fire-

places listed to UL 127 conforming to the following speci-

fications and instructions:

•The original factory-built clearance fireplace chimney

cap must be re-installed after installing the approved

chimney liner meeting type UL 103 HT requirements

(2100°F) per UL 1777.

•If the chimney is not listed as meeting HT requirements,

or if the factory built fireplace was tested prior to 1998, a

full height listed chimney liner must be installed from the

appliance flue collar to the chimney top.

•The liner must be securely attached to the insert flue collar

and the chimney top.

•The air flow of the factory-built zero-clearance fireplace

system must not be altered. The flue liner top support

attachment must not reduce the air flow for the existing

air-cooled chimney system.

•No dilution air is allowed to enter the chimney.

1. Secure the fireplace damper in the open position. If

this cannot be accomplished, it will be necessary to

remove the damper

2. Seal damper area of chimney around chimney

connector with a high temperature sealant or seal

insert against the face of the fireplace.

3. Both methods must be removable and replaceable

for cleaning and re-installation.

Advertising
This manual is related to the following products: