CB1200-I Pellet Insert

R

R

3 in. or 4 in. (76mm or 102mm) Diameter Pipe

Equivalent Pipe

Length In Feet

ALTITUDE IN THOUSANDS OF FEET

0

20

30

1 2 3 4 5 6 7 8 9 10

4 in. (102mm) Diameter Pipe Only

10

Example 1

Example 2

Improper installation, adjustment, alteration, service or

maintenance can cause injury or property damage. Refer

to the owner’s information manual provided with this appli-

ance. For assistance or additional information consult a

qualified installer, service agency or your dealer.

WARNING

The chart will help you in determing proper venting

size according to the equivalent feet of pipe calcuated

above and the altitude above sea level of this installa-

tion. See Figure 14.2.
Locate the calculated equivalent feet of pipe on

the vertical left side of the chart. Move to the right

horizontally on the chart until you reach your altitude

above sea level.
If you fall below the diagonal line, 3 or 4 inch (76 to

102mm) pipe may be used. If it is anywhere above

the diagonal line, a 4 inch (102mm) diameter pipe is

requried.
The chart reveals that a 90° elbow is 5 times as

restrictive to the flow of exhaust gases under positive

pressure as 1 foot of horizontal pipe, and a foot of

horizontal pipe is twice as restrictive as a foot of

vertical pipe.

D. Pipe Selection Chart

The table below can help you calculate the equivalent feet of

pipe which is a method used to determine pellet vent size. See
Figure 14.1.

C. Equivalent Feet of Pipe

2 ft.

2 ft.

3 ft.

2 ft.

Example of 3 Elbow-Rear Vent Termination Calculation

Figure 14.1

Figure 14.2

Pellet Venting

Component

# of

Elbows

Feet of

Pipe

Multiplied

By

Equivalent

Feet

Components

Equivalent Feet

90

o

Elbow or Tee

3

X

5

15

45

o

Elbow

X

3

Horizontal Pipe

7

X

1

7

Vertical Pipe

2

X

0.5

1

Total Equivalent Feet

23

Note: This is a generic example and is not

intended to represent any specific fuel type.

Fire Risk.
Do NOT pack insulation or other combustibles between firestops.
• ALWAYS maintain specified clearances around venting and firestop systems.

• Install firestops as specified.
Failure to keep insulation or other material away from vent pipe may cause fire.

WARNING

Example 1

: If the equivalent length of pipe is 23 feet (7m)with altitude

of 8,000 feet (2438m) you must use 4 inch (102mm) diameter type “L”

or “PL” vent.
Example 2

: If the equivalent length of pipe is 12 feet (3.7m) with al-

titude of 6,000 feet (1829m) you may use 3 or 4 inch (76 to 102mm)

diameter type “L” or “PL” vent