Mobile home, Warning, Caution – Quadra-Fire PELLET INSERT CB1200MI-MBK User Manual

Page 17

Advertising
background image

R

R

R

February 3, 2010

7014-188B

Page 17

CB1200-I Pellet Insert

6

Mobile Home

1. An outside air inlet must be provided for the combustion

air and must remain clear of leaves, debris, ice and/or

snow. It must be unrestricted while the appliance is

in use to prevent room air starvation which causes

smoke spillage. Smoke spillage can also set off smoke

alarms.

2. The combustion air duct system must be made of metal.

It must permit zero clearance to combustible construc-

tion and prevent material from dropping into the inlet or

into the area beneath the dwelling and contain a rodent

screen.

3. The appliance must be secured to the mobile home

structure by bolting it to the floor (using lag bolts) in two

places. Use the same holes that secured the appliance

to the shipping pallet.

4. The appliance must be grounded with #8 solid copper

grounding wire or equivalent, terminated at each end

with an NEC approved grounding device.

5. Refer to Clearances to Combustibles and floor pro-

tection requirements on pages 9 & 10 for listings to

combustibles and appropriate chimney systems.

6. Use silicone to create an effective vapor barrier at

the location where the chimney or other component

penetrates to the the exterior of the structure.

7. Follow the chimney manufacturer’s instructions when

installing the vent system for use in a mobile home.

8. Installation shall be in accordance with the Manufactur-

ers Home & Safety Standard (HUD) CFR 3280, Part

24.

Installation must comply with Manufactured Home and

Safety Standard (HUD), CFR 3280, Part 24.

WARNING

You must use a Quadra-Fire Outside Air Kit
for installation in a mobile home.

A. Mobile Home Installation

Spark Arrestor Cap

Roof Flashing

Storm Collar

Joist Shield/Firestop

Approved Class “L”

or “PL” Pellet Vent

Figure 17.1

CAUTION

Never draw outside combustion air from:

• Wall, floor or ceiling cavity

• Enclosed space such as an attic or garage

CAUTION

THE STRUCTURAL INTEGRITY OF THE MOBILE HOME

FLOOR, WALL AND CEILING/ROOF MUST BE MAIN-

TAINED
Do NOT cut through:

• Floor joist, wall, studs or ceiling trusses.

• Any supporting material that would affect the structural

integrity.

NEVER INSTALL IN A SLEEPING ROOM.
Consumes oxygen in the room.

WARNING

Asphyxiation Risk.