Instructions fun 101 <= less than or equal – Toshiba 6F3B0253 User Manual

Page 185

Advertising
background image

6F3B0253

Basic Hardware and Function

183

7. Instructions

FUN 101

<=

Less than or equal

Expression

Input

[ A

<=

B ]

Output

Function

When the input is ON, the data of A and the data of B are compared, and if A is less than or equal
to B, the output is turned ON.

Execution condition

Input

Operation

Output

OFF

No execution

OFF

ON

Execution

A

B

ON

A

>

B

OFF

Operand

Name

Device

Register

Constant Index

X

Y

R

S

T.

C. XW YW RW SW T

C

D

I

J

K

A Compared

data

B Reference

data

Example

When R00C is ON, the data of D0125 is compared with the constant data -100, and if the data
of D0125 is less than or equal to -100, R020 is turned ON.

If the data of D0125 is -150, the comparison result is true. Consequently, R020 is turned ON.

D0125

-150

<

Constant

-100

R020 is ON

If the data of D0125 is 0, the comparison result is false. Consequently, R020 is turned OFF.

D0125

0

Constant

-100

R020 is OFF

Note

This instruction deals with the data as signed integer (-32768 to 32767).

Advertising