10. Troubleshooting

10.1.1 Power supply check

If the PWR (power) LED is not lit after power on, check the following points.

Check the power connection

Connection terminals are correct.
The terminal screws are not loose.
The terminal block is installed securely.

Correct

Check the power voltage

85 to 132/170 to 264Vac (50/60 Hz)

at the T1-16S’s terminal

or 20.4 to 28.8Vdc (DC power)

Normal

Remove the programmer

If the PWR LED becomes normal, the

port connector

internal 5Vdc can be shorted in the
external connections of this port.

Still unlit

Remove the 24Vdc service

If the PWR LED becomes normal, the

power terminals if it is used

24Vdc service power can be over load.

Still unlit

Remove the I/O modules.

If the PWR LED is still unlit, the T1-16S
basic unit may be faulty. Replace the unit.

Lit

Confirm the internal 5Vdc

The 5Vdc capacity for I/O modules is

current consumption if

max. 1.5A.

I/O module is used.

(Refer to section 2.1.)

Within the limit

Insert the removed option

Replace the faulty I/O module.

modules one by one to
pinpoint the faulty card.