6F3B0253

Basic Hardware and Function

189

7. Instructions

FUN 107

D

<=

Double-word less than or equal

Expression

Input

−

[ A+1

⋅

A D

<=

B+1

⋅

B ]

−

Output

Function

When the input is ON, the double-word data of A+1

⋅

A and B+1

⋅

B are compared, and if A+1

⋅

A is

less than or equal to B+1

⋅

B, the output is turned ON.

Execution condition

Input

Operation

Output

OFF

No execution

OFF

ON

Execution

A+1

⋅

A

≤

B+1

⋅

B

ON

A+1

⋅

A

>

B+1

⋅

B

OFF

Operand

Name

Device

Register

Constant Index

X

Y

R

S

T.

C. XW YW RW SW T

C

D

I

J

K

A Compared

data

√

√

√

√

√

√

√

√

B Reference

data

√

√

√

√

√

√

√

√

Example

When R010 is ON, the data of D0101

⋅

D0100 is compared with the constant data 0, and if the

data of D0101

⋅

D0100 is less than or equal to 0, R014 is turned ON.

If the data of D0101

⋅

D0100 is -1, R014 is turned ON.

D0101

⋅

D0100 -1

≤

Constant

0

R014 is ON

If the data of D0101

⋅

D0100 is 10000, R014 is turned OFF.

D0101

⋅

D0100 10000

>

Constant

0

R014 is OFF

Note

•

This instruction deals with the data as double-word integer (-2147483648 to 2147483647).