Instructions fun 146 stot step sequence output – Toshiba 6F3B0253 User Manual

Page 216

Advertising
background image

6F3B0253

214

T1-16S User’s Manual

7. Instructions

FUN 146

STOT

Step sequence output

Expression

Input

−

[ STOT A ]

−

Function

When the input is ON, the device A is set to ON and the devices of STIN instructions on the same
rung are reset to OFF.

Execution condition

Input

Operation

Output

OFF

No execution

-

ON

Execution

-

Operand

Name

Device

Register

Constant Index

X

Y

R

S

T.

C. XW YW RW SW T

C

D

I

J

K

A Step device

√

Example

See example on STIN (FUN 145) instruction.

Note

•

The STIZ, STIN and STOT instructions are used together to configure the step sequence.

•

Two or more STOT instructions can be placed on one rung to perform simultaneous sequences.

•

Two or more STIN instructions can be placed on one rung in parallel or in series to perform loop

or convergence of sequences. (Max. 11 STIN instructions on one rung)

•

To perform the conditional branch (sequence selection), separate the rungs as follows.

This limitation is applied to T1 version 1.00 only.

[ STIN A ]

| |

[ STOT B ]

[ STIN A ]

| |

[ STOT B ]

| |

[ STOT C ]

[ STIN A ]

| |

[ STOT C ]

Not allowed

Available