7. Instructions

Data table:

Register

Data contents

Signal direction

D2000

#0 Operating frequency

←

Read

D2001

#0 Output terminal status

←

Read

D2002

#0 Frequency reference

→

Write

D2003

#0 Operation command

→

Write

D2004

#1 Operating frequency

←

Read

D2005

#1 Output terminal status

←

Read

D2006

#1 Frequency reference

→

Write

D2007

#1 Operation command

→

Write

D2020

#5 Operating frequency

←

Read

D2021

#5 Output terminal status

←

Read

D2022

#5 Frequency reference

→

Write

D2023

#5 Operation command

→

Write

•

The data format for the operating frequency and the frequency reference registers are 0.01 Hz units.
For example, if it is 60 Hz, the corresponding register data is 6000.

•

For the data format of the output terminal status register, refer to the Monitor mode (mode 1).

•

The bit assignment of the operation command register is as follows. For details, refer to your
Inverter manual.

F

E

D

C

B

A

9

8

7

6

5

4

3

2

1

0

Programmed speed selection

0000 = None
0001 = Speed 1
0010 = Speed 2
:
1111 = Speed 15

PI operation (0 = Normal / 1 = Off)

DC braking (0 = Off / 1 = On)

Jog operation (0 = off / 1 = On)

F/R selection (0 = Forward / 1 = Reverse)

Run/Stop (0 = Stop / 1 = Run)

Free run (0 = Normal / 1 = Free run)

Emergency stop (0 = Normal / 1 = EMS)

Reset command (0 = Normal / 1 = Reset)

Frequency enable (0 = Disable / 1 = Enable)

Command enable (0 = Disable / 1 = Enable)

Example operation:

To operate the #0 Inverter at 30 Hz forward rotation, write the value 3000 in D2002 and HC400 in
D2003. (HC400 = Bits F, E, A are 1, and others are 0)
The current operating frequency and the output terminal status of the #0 Inverter are stored in D2000
and D2001 respectively.