Instructions – Toshiba 6F3B0253 User Manual

Page 250

Advertising
background image

6F3B0253

248

T1-16S User’s Manual

7. Instructions

Data table:

Register

Data contents

Signal direction

D2000

#0 Operating frequency

Read

D2001

#0 Output terminal status

Read

D2002

#0 Frequency reference

Write

D2003

#0 Operation command

Write

D2004

#1 Operating frequency

Read

D2005

#1 Output terminal status

Read

D2006

#1 Frequency reference

Write

D2007

#1 Operation command

Write

D2020

#5 Operating frequency

Read

D2021

#5 Output terminal status

Read

D2022

#5 Frequency reference

Write

D2023

#5 Operation command

Write

The data format for the operating frequency and the frequency reference registers are 0.01 Hz units.
For example, if it is 60 Hz, the corresponding register data is 6000.

For the data format of the output terminal status register, refer to the Monitor mode (mode 1).

The bit assignment of the operation command register is as follows. For details, refer to your
Inverter manual.

F

E

D

C

B

A

9

8

7

6

5

4

3

2

1

0

Programmed speed selection

0000 = None
0001 = Speed 1
0010 = Speed 2
:
1111 = Speed 15

PI operation (0 = Normal / 1 = Off)

DC braking (0 = Off / 1 = On)

Jog operation (0 = off / 1 = On)

F/R selection (0 = Forward / 1 = Reverse)

Run/Stop (0 = Stop / 1 = Run)

Free run (0 = Normal / 1 = Free run)

Emergency stop (0 = Normal / 1 = EMS)

Reset command (0 = Normal / 1 = Reset)

Frequency enable (0 = Disable / 1 = Enable)

Command enable (0 = Disable / 1 = Enable)

Example operation:

To operate the #0 Inverter at 30 Hz forward rotation, write the value 3000 in D2002 and HC400 in
D2003. (HC400 = Bits F, E, A are 1, and others are 0)
The current operating frequency and the output terminal status of the #0 Inverter are stored in D2000
and D2001 respectively.