Installation and wiring, Caution – Toshiba 6F3B0253 User Manual

Page 56

Advertising
background image

6F3B0253

54

T1-16S User’s Manual

4. Installation and Wiring

4.1 Environmental conditions

Do not install the T1-16S in the following locations:

•

Where the ambient temperature drops below 0

°

C or exceeds 55

°

C.

•

Where the relative humidity drops below 20% or exceeds 90%.

•

Where there is condensation due to sudden temperature changes.

•

In locations subject to vibration that exceeds tolerance.

•

In locations subject to shock that exceeds tolerance.

•

Where there are corrosive or flammable gases.

•

In locations subject to dust, machining debris or other particles.

•

In locations exposed to direct sunlight.

Observe the following precautions when installing enclosures in which the T1-16S will
be installed:

•

Provide the maximum possible distance from high-voltage or high-power panels.

This distance must be at least 200mm.

•

If installing the enclosures in the vicinity of high-frequency equipment, be sure to

correctly ground the enclosures.

•

When sharing the channel base with other panels, check for leakage current from

the other panels or equipment.

!

CAUTION

Excess temperature, humidity, vibration, shocks, or dusty and corrosive
gas environment can cause electrical shock, fire or malfunction.
Install and use the T1-16S and related equipment in the environment
described in this section.

Advertising