Programming information – Toshiba 6F3B0253 User Manual

Page 84

Advertising
background image

6F3B0253

82

T1-16S User’s Manual

6. Programming Information

Device/

register

Name

Function

S050

CF (carry flag)

Used for instructions which manipulate carry

S051

ERF (instruction error flag) ON when instruction execution error is occurred

(related to alarm flags of SW06)

S052

−

Reserved

S053

−

Reserved

S054

−

Reserved

S055

−

Reserved

S056

−

Reserved

S057

−

Reserved

S058

−

Reserved

S059

−

Reserved

S05A

−

Reserved

S05B

−

Reserved

S05C

−

Reserved

S05D

−

Reserved

S05E

−

Reserved

S05F

−

Reserved

S060

Illegal instruction (down)

ON when illegal instruction is detected

S061

−

Reserved

S062

−

Reserved

S063

−

Reserved

S064

Boundary error (alarm)

ON when illegal address is designated by indirect
addressing (operation continued)

S065

−

Reserved

S066

−

Reserved

S067

−

Reserved

S068

Division error (alarm)

ON when error occurs in division instruction (operation
continued)

S069

BCD data error (alarm)

ON when BCD data error has detected in BCD
operation instructions (operation continued)

S06A

Table operation error
(alarm)

ON when table size error has detected in table
operation instructions (operation continued) (T1S only)

S06B

Encode error (alarm)

ON when error occurs in encode instruction (operation
continued)

S06C

−

Reserved

S06D

−

Reserved

S06E

−

Reserved

S06F

−

Reserved

NOTE

(1) Devices marked as (down) are set in the ERROR mode. Therefore

these devices cannot be used in the user program.

(2) CF, ERF and devices marked as (alarm) can be reset by the user

program.