Toshiba Carrier RAV-SP180UT-UL EN User Manual

Page 12

Advertising
background image

Toshiba

– 11 –

4-way Air Discharge Cassette Type

Installation Manual

• Attach a nut (3/8" (M10): not supplied) and the Ø1.3"

(34 mm) washer (supplied) to each hanging bolt.

• Insert a washer on both sides of the T groove of the

hanging bracket of the indoor unit, and hang the
indoor unit.

• Check that the four sides of the indoor unit are level

using a level vial (levelness: 0.2" (5 mm) or less).

• Detach the installation gauge (accessory) from the

installation pattern.

• Using the installation gauge, check and adjust the

positional relation between the indoor unit and the
ceiling opening (1) (0.4” - 1.4” (10 - 35 mm): 4 sides)
and the hanging-up height (2) (0.5” - 0.7” (12 - 17
mm): 4 corners).
(How to use the installation gauge is printed on the
gauge.)

REQUIREMENT

Before installation of the indoor unit, be sure to remove
the cushion for transportation between the fan and the
bell mouth. Running the unit without removing the
cushion may damage the fan motor.

Washer (Accessory)
To prevent the bolt

from falling off (for

safety), be sure to set

it just under the

hanging bracket as

shown in the figure.

Eccentric washer

(Accessory)

Nut

3/8” (M10)

Hanging bolt

3/8” (M10)

Nut

3/8” (M10)

* Procure hanging bolts

and nuts locally.

* Install with the marking

“UP” facing up.

Indoor unit

Level vial (levelness: 0.2” (5 mm) or less)

Hanging bolt

Hanging

bracket

Installation gauge

(1) 0.4” - 1.4”

(10 - 35 mm)

Ceiling

board

(2)

0.5” -

0.7”

(12 - 17mm)

Indoor unit

Installation gauge

(1) 0.4” - 1.4”

(10 - 35 mm)

(2) 0.5” - 0.7”

(12 - 17 mm)

Ceiling board

Remove the 5 screws and detach the

wire guard. Remove the cushion

placed between fan and bell mouth.

Attach back the wire guard.

Wire guard

Screw

Screw

Screw

Cushion

Clamp
* Do not remove the

clamp fixing screw on

the indoor unit.

11-EN

+00EH99864701_00Ta.book Page 11 Tuesday, November 24, 2009 4:54 PM

Advertising