– 35 –

4-way Air Discharge Cassette Type

Installation Manual

F31

(L29)

SIM

Outdoor unit P.C.
board

Outdoor

Outdoor P.C. board ---- In the case of EEPROM error.

Entire stop

H01

Outdoor unit
compressor
breakdown

Outdoor

Current detect circuit, power voltage --- Minimum
frequency was reached in the current releasing control or
short-circuit current (Idc) after direct excitation was
detected
Wiring error of compressor (open phase)

Entire stop

H02

Outdoor unit
compressor lock

Outdoor

Compressor circuit --- Compressor lock was detected.
Wiring error of compressor (open phase)

Entire stop

H03

Outdoor unit current
detect circuit error

Outdoor

Current detect circuit, outdoor unit P.C. board ---
Abnormal current was detected in AC-CT or a phase loss
was detected.

Entire stop

H04

(P04)

Case thermostat
operation

Outdoor

Malfunction of the case thermostat

Entire stop

H06

Outdoor unit low-
pressure system error

Outdoor

Current, high-pressure switch circuit, outdoor P.C. board
--- Ps pressure sensor error was detected or low-pressure
protective operation was activated.

Entire stop

L03

SIM

Duplicated header
indoor units

Indoor

Indoor address setting error --- There are two or more
header units in the group.

Entire stop

L07

SIM

Group line in individual
indoor unit

Indoor

Indoor address setting error --- There is at least one
group-connected indoor unit among individual indoor
units.

Entire stop

L08

SIM

Indoor group address
not set

Indoor

Indoor address setting error --- Indoor address group has
not been set.

Entire stop

L09

SIM

Indoor power level not
set

Indoor

Indoor power level has not been set.

Entire stop

L10

(L29)

SIM

Outdoor unit P.C.
board

Outdoor

In the case of outdoor P.C. board jumper wire (for service)
setting error

Entire stop

L20

SIM

LAN communication
error

Network
adapter
central
control

Address setting, central control remote control, network
adapter --- Duplication of address in central control
communication

Auto-reset

L29

SIM

Other outdoor unit
error

Outdoor

Other outdoor unit error

Entire stop

1) Communication error between IPDU MCU and CDB
MCU

Entire stop

2) Abnormal temperature was detected by the heat sink
temp. sensor in IGBT.

L30

SIM

Abnormal external
input into indoor unit
(interlock)

Indoor

External devices, outdoor unit P.C. board --- Abnormal
stop due to incorrect external input into CN80

Entire stop

L31

SIM

Phase sequence error,
etc.

Outdoor

Power supply phase sequence, outdoor unit P.C. board -
-- Abnormal phase sequence of the 3-phase power
supply

Operation
continued

(thermostat

OFF)

P01

ALT

Indoor unit fan error

Indoor

Indoor fan motor, indoor P.C. board --- Indoor AC fan
error (fan motor thermal relay activated) was detected.

Entire stop

P03

ALT

Outdoor unit discharge
temp. error

Outdoor

An error was detected in the discharge temp. releasing
control.

Entire stop

P04

ALT

Outdoor unit high-
pressure system error

Outdoor

High-pressure switch --- The IOL was activated or an
error was detected in the high-pressure releasing control
using the TE.

Entire stop

P05

(P04)

ALT

Open phase detected

Outdoor

The power cable may be connected incorrectly. Check
open phase and voltages of the power supply.

Entire stop

P07

ALT

Heat sink overheat

Outdoor

Abnormal temperature was detected by the temp. sensor
of the IGBT heat sink.

Entire stop

P10

ALT

Indoor unit water
overflow detected

Indoor

Drain pipe, clogging of drainage, float switch circuit,
indoor P.C. board --- Drainage is out of order or the float
switch was activated.

Entire stop

P15

(L29)

ALT

Gas leakage detected

Outdoor

There may be gas leakage from the pipe or connecting
part. Check for gas leakage.

Entire stop

P19

(L29)

ALT

4-way valve error

Outdoor
(Indoor)

4-way valve, indoor temp. sensors (TC/TCJ) --- An error
was detected due to temperature drop of the indoor unit
heat exchanger sensor when heating.

Auto-reset

(Auto-reset)

P20

(P04)

ALT

High-pressure
protective operation

Outdoor

High-pressure protection

Entire stop

35-EN