Installation Manual

„

System interconnection wires
and ground wire

1. Strip the wire ends.

System interconnection wire : 0.4” (10 mm)
Ground wire : 0.8” (20 mm)

2. Match the wire colors with the terminal numbers on

the indoor and outdoor units’ terminal blocks and
firmly screw the wires to the corresponding
terminals.

3. Secure the ground wire with the ground screw.
4. Fix the wires with a cord clamp.

Unit: in (mm)

CAUTION

• Firmly tighten the screws of the terminal block.

Keep the wire length as shown in figure below when it
is connected to the terminal block.

„

Wiring on the ceiling panel

According to the Installation Manual of the ceiling
panel, connect the connector (20P: White) of the
ceiling panel to the connector (CN510: White) on P.C.
board of the electric parts box.

„

Remote Control Wiring

• Strip off the wire approx. 0.4” (9 mm) to connect.
• For a single system, use non polarity, 2 core wire for

the remote control wiring. (2 x AWG 20)

• For the details of wiring/installation of the remote

control, refer to the Installation Manual enclosed with
the remote control.

„

Wiring diagram

Single system

L

1

S

L

2

0.8” (20)

1.2” (30)

0.4” (10)

Ground wire

0.08”

(2 mm)

or less

System

interconnection wire

A
B

A
B

Terminal block

Remote

control

unit

Terminal block for

remote control wiring

of indoor unit

Remote control wire

(Field procurement)

A B

L

1

L

1

L

2

L

2

S

S

208/230-1-60

Indoor unit

Outdoor

unit

Remote

control

Low voltage

High voltage

21-EN