EN

„

Wire connection

REQUIREMENT

• Be sure to connect the wires matching the terminal numbers. Incorrect connection causes a trouble.
• The low-voltage circuit is provided for the remote control. (Do not connect the high-voltage circuit)

• Remove the cover of the electric parts box by taking off the mounting screws (2 positions) and pushing the

hooking section. (The cover of the electric parts box remains hanged to the hinge.)

• Remove the 2 screws from the wire cover.
• Attach the conduit pipe to the conduit plate with a lock nut.
• Connect the system interconnection wires and remote control wire to the terminal block of the electric parts box.

Secure the ground wire with the ground screw.

• Tighten the screws of the terminal block, and fix the wires with cord clamp attached to the electric parts box.

(Do not apply tension to the connecting section of the terminal block.)

• Mount the wire cover without catching the wires. (The wire cover should be mounted before the ceiling panel.)
• Mount the cover of the electric parts box without catching the wires.

(Mount the cover after wiring on the ceiling panel.)

Thermal insulation to wiring connecting port

A

B

L

1

L

2

S

Hinge

Electric parts

box cover

Wire cover

Screws at 2 positions

Louver connector

(CN510: White)

Power supply

terminal block

Conduit

connection hole

Piping

Knockout

Hole for remote

control wires

Lock nut

Conduit pipe

Conduit plate

Remote

control

terminal block

Cord clamp

Side D

(Space: 0.33” (8.5 mm))

Side C

(Space: 0.16” (4 mm))

Insert the wire to Side C.

Ground screw

20-EN