Filter sign setting

According to the installation condition, the lighting time
of the filter sign (Notification of filter cleaning) can be
changed.
Follow to the basic operation procedure
(

1

2

3

4

5

6

).

• For the CODE No. in Procedure

3

, specify [01].

• For the [Set data] in Procedure

4

, select the setup

data of filter sign lighting time from the following
table.

„

To secure better effect of
heating

When it is difficult to obtain satisfactory heating due to
installation place of the indoor unit or structure of the
room, the detection temperature of heating can be
raised. Also use a circulator, etc. to circulate heat air
near the ceiling.
Follow to the basic operation procedure
(

1

2

3

4

5

6

).

• For the CODE No. in Procedure

3

, specify [06].

• For the set data in Procedure

4

, select the setup

data of shift value of detection temperature to be set
up from the table below.

„

Horizontal louver direction

1. Push

and TEMP.

buttons for at least four

seconds when the air conditioner is not working.

flashes.

Indicates CODE No. “01.”

2. Select an indoor unit to be set by pushing

button (left side of the button).
Indoor unit number changes each time you push the
button.

The fan of the selected unit runs and the louvers
start swinging.

3. Change the CODE No. to “45” with TEMP.

buttons.

4. Select louver direction setting with TIME

buttons.

5. Push

button to check the setting.

The display state changes from flashing to lighting,
and the setting is fixed.

6. Push

button to end the setting.

* When the cold draft position is selected, ceiling

contamination is less reduced.

Setup data

Filter sign lighting time

0000

None

0001

150 H

0002

2500 H (Factory default)

0003

5000 H

0004

10000 H

Setup

data

Detection temp shift value

0000

No shift

0001

+1.8 °F (+1 °C)

0002

+3.6 °F (+2 °C)

(Factory default)

0003

+5.4 °F (+3 °C)

0004

+7.2 °F (+4 °C)

0005

+9.0 °F (+5 °C)

0006

+10.8 °F (+6 °C)

Louver

direction

setting code

Louver direction setting

0000

Smudge reducing position

(Air direction to reduce ceiling

contamination) [Factory default]

0002

Cold draft position

(Air direction to control cold air fall)

Not

display

UNIT No.