Installing indoor unit on high ceiling, Using wireless remote control – Toshiba Carrier RAV-SP180UT-UL EN User Manual

Page 24

Advertising
background image

Toshiba

– 23 –

4-way Air Discharge Cassette Type

Installation Manual

Procedure

3

Using temp. setup

/

buttons, specify CODE

No. [

].

Procedure

4

Using timer time

/

buttons, select SET DATA

[

].

Procedure

5

Push

button. When the display changes from

flashing to lit, the setup is completed.
• To change settings of another indoor unit, repeat

from Procedure

2

.

• To change other settings of the selected indoor unit,

repeat from Procedure

3

.

Use

button to clear the settings.

To make settings after

button was pushed, repeat

from Procedure

2

.

Procedure

6

When settings have been completed, push

button

to determine the settings.
When

button is pushed, “SETTING” flashes and

then the display content disappears and the air
conditioner enters the normal stop mode.
(While “SETTING” is flashing, no operation of the
remote control is accepted.)

„

Installing indoor unit on high
ceiling

When an indoor unit is installed on a ceiling higher than
the standard height, make the high-ceiling setting for
fan speed adjustment.
Follow to the basic operation procedure
(

1

2

3

4

5

6

).

• For the CODE No. in Procedure

3

, specify [5d].

• Select the setting data for Procedure

4

from the

“Height list of ceiling possible to be installed” table on
page 7 in this manual.

„

Using wireless remote control

Change the high-ceiling settings with the DIP switch on
the receiver section P.C. board.
For details, refer to the manual of the wireless remote
controller kit. The settings can also be changed with
the switch on the indoor microcomputer P.C. board.
* However, once the setting is changed, setting to

0001 or 0003 is possible but setting to 0000 requires

a setting data change to 0000 using the wired remote

control (sold separately) with the normal switch

setting (factory default).

Restore the factory default

To return the DIP switch settings to the factory default,
set SW501-1 and SW501-2 to OFF, connect a
separately sold wired remote control, and then set the
data of CODE No. [5d] to “0000”.

Setup data

SW501-1

SW501-2

0000

(Factory default)

OFF

OFF

0001

ON

OFF

0003

OFF

ON

SW501-1

MCU(IC501)

SW501-2

23-EN