Toshiba

– 36 –

4-way Air Discharge Cassette Type

Installation Manual

EN

Check codes in parentheses ( ) are displayed when connected to an outdoor unit other than the new SDI series.

: Lighting

: Flashing

: OFF

: The air conditioner automatically enters the auto-address setting mode.

ALT: When two LEDs are flashing, they flash alternately. SIM: When two LEDs are flashing, they flash in synchronization.
Receiving unit display OR: Orange GR: Green

P22

ALT

Outdoor unit fan error

Outdoor

Outdoor unit fan motor, outdoor unit P.C. board --- An
error (overcurrent, locking, etc.) was detected in the
outdoor unit fan drive circuit.

Entire stop

P26

ALT

Outdoor unit inverter
Idc activated

Outdoor

IGBT, outdoor unit P.C. board, inverter wiring,
compressor --- Short-circuit protection for compressor
drive circuit devices (G-Tr/IGBT) was activated.

Entire stop

P29

ALT

Outdoor unit position
error

Outdoor

Outdoor unit P.C. board, high-pressure switch ---
Compressor motor position error was detected.

Entire stop

P31

ALT

Other indoor unit error

Indoor

Another indoor unit in the group is raising an alarm.

Entire stop

E03/L07/L03/L08 alarm check locations and error
description

Auto-reset

36-EN