Functions, Initial setting – Toshiba TOSVERT VF-S15 series option unit Function E6581830 User Manual

Page 13

Advertising
background image

E658130

- 12 -

5.

Functions

This option is a communication interface unit that allows the PLC program to operate, monitor
and set the parameter of the inverter as a remote station of CC-Link. It is able to communicate
with a maximum speed of 10Mbps not only transmitting bit data but also by word data.
Moreover, more data transmissions are possible by the use of CC-Link V2.0.

5.1. Initial setting

Set the following parameters of the inverter.

Title

Function Description

Factory

setting

CC-Link

setting

cmod

Command mode
selection

0: Terminal board
1: Panel keypad (including remote keypad)
2: RS485 communication
3: CANopen communication
4: Communcation option

1 4

fmod

Frequency setting
mode selection 1

0: Setting dial 1 (save even if power is off)
1: Terminal board VIA
2: Terminal board VIB
3: Setting dial 2 (press in center to save)
4: RS485 communication
5: UP/DOWN from external logic input
6: CANopen communication
7: Communication option
8: Terminal board VIC
9, 10: -
11: Pulse train input

12, 13: -
14: sro

0 7

f856

Number of motor
pole for
communication

1: 2 poles
2: 4 poles
3: 6 poles
4: 8 poles
5: 10 poles
6: 12 poles
7: 14 poles
8: 16 poles

2 *

f899

Communication
function reset

0: -
1: Reset (after execution: 0)

0 -

*Set parameter according to number of motor pole used.