6.2.

Program example for setting the operation mode

Example 2 shows

a ladder logic to

write data in the inverter.

The operation mode of station 1 inverter can be changed to network operation.
Operation mode writing code number: 2003H (hexadecimal)
Network operation set data: 0004H (hexadecimal)
The reply code at the time of instruction code execution is set to D2.






























Check the ready of the station 1

Write operation mode write code
(2003H) to RWw2 and set data
(0004H) to RWw3.

X0

X0F X1

( M0)

SW80.0

M0

X20

[ PLS M300]

M300

[ SET M301]

M301

X100F

[ MOV H2003 W102]

[ MOV H0004 W103]

[ SET Y100F]

[ RST M301]

[ SET M302]

M302

X100F

[ MOV W2 D2]

[ RST Y100F]

[ RST M302]

[ END]

Turn on the instruction code
execution

Read reply code (RWr2) to D2 when the
Instruction code execution completion
flag

Turn off the instruction code
execution

Example