Unusual diagnosis, Option error, Disconnection error of network cable – Toshiba TOSVERT VF-S15 series option unit Function E6581830 User Manual

Page 48

Advertising
background image

E658130

- 47 -

7.

Unusual diagnosis

7.1. Option error

The error message is displayed when there is hardware error, software error or lose of
connection of wire.


Display of trip information

e

-

23

(Optional unit fault 2 : 0037H) : Option error

7.2. Disconnection error of network cable

▼Display of trip information

err8

(

Optional unit fault 1

: 001BH):

Network error stop

*If a network error occurs when c101 is set to "4", it is displayed.

Related parameter

Title Function Setting

range

Description

c100

Communication error
detection delay time

0.0 to100.0 sec

The waiting time from when a network error occurs
can be adjusted. If a network error continues past the
time set in c100, it is recognized as a
communication error and the operation of the inverter
follows the setting of c101.
When normal communication returns during the
setting time, a communication error is not displayed
and operation is continued.

*

Time-out time

= CC-Link network time out

+ c100

(communication error detection delay time) [0.1s]

c101

Inverter operation at the
communications loss action

0 to 5

The operation of the drive when the communication
fault occurs can be specified.

c102

Preset speed operation
selection

0 to 15

The operation frequency of the drive when the
communication fault occurs can be specified. (Only
when c101 is set to 5)

c103

Communication time-out
condition selection

0 to 2

Select the communication time-out condition.


Advertising