5.3.3. CC-Link extended setting

Remote register function can be extended.

Title

Function Description

c122

*

CC-Link extended selection

0: Occupies one station (V1.10)
1: Occupies one station double (V2.0)
2: Occupies one station quadruple (V2.0)
3: Occupies one station octuple (V2.0)


When using double, quadruple and octuple settings of the CC-Link Ver.2, station data

of the master station must be set to double, quadruple and octuple also.
(If the master station is CC-Link Ver.1 compatible station, the above setting can not be
made.)