When two or more inverters are connected – Toshiba TOSVERT VF-S15 series option unit Function E6581830 User Manual

Page 50

Advertising
background image

E658130

- 49 -

2.When two or more inverters are connected

The following example explains the causes and corrective actions for fault which may be
judged from the LED status of the CC-Link units (CCL003Z) of the inverters under the
condition that the SW, M/S and PRM LEDs of the master unit are off (the master unit setting is
proper) in the system configuration shown below:




PS:
Power
supply

LED Status

CCL003Z

Master

Station

1 Station

2 Station

3

Cause Corrective

Action

L.RUN

●

L.RUN

●

L.RUN

●

SD

●

SD

●

SD

●

RD

●

RD

●

RD

●

L.ERR

○

L.ERR

○

L.ERR

○

Normal

-

L.RUN

○

L.RUN

●

L.RUN

●

SD

○

SD

●

SD

●

RD

○

RD

●

RD

●

TIME○

LINE○

or

TIME●

LINE○

L.ERR

○

L.ERR

○

L.ERR

○

Poor contact of the
CCL003Z with the
Inverter or the power
supply is not supplied.

Plug the CCL003Z
securely.
Check the connector.

L.RUN

●

L.RUN

○

L.RUN

○

SD

●

SD

*

SD

*

RD

●

RD

*

RD

*

L.ERR

○

L.ERR

○

L.ERR

○

Since the L.RUN LEDs
of station 2 and later are
off, the communication
cable between the unit 1
and 2 is open or
disconnected from the
terminal block.

Referring to the LED
"on" condition, search
for an open point and
repair.

L.RUN

○

L.RUN

○

L.RUN

○

SD

*

SD

*

SD

*

RD

*

RD

*

RD

*

L.ERR

○

L.ERR

○

L.ERR

○

The communication
cable is shorted.

Among the three wires
of the communication
cable, search for
shorted wire and
repair.

L.RUN

○

L.RUN

○

L.RUN

○

SD

*

SD

*

SD

*

RD

*

RD

*

RD

*

TIME●

LINE●

or

TIME○

LINE●

L.ERR

*

L.ERR

*

L.ERR

*

The communication
cable is wired improperly.

Check the wiring on
CCL003Z terminal
block and correct the
improper wiring point.

●

:

On,

○:

OFF, ◎:

Flicker,

*:

Any of on, flicker or off.

Master

CPU Unit

Station

1

Inverter

P

S

Station

2

Inverter

Station

3

Inverter