When two or more inverters are connected – Toshiba TOSVERT VF-S15 series option unit Function E6581830 User Manual

Page 50

Advertising
background image

E658130

- 49 -

2.When two or more inverters are connected

The following example explains the causes and corrective actions for fault which may be
judged from the LED status of the CC-Link units (CCL003Z) of the inverters under the
condition that the SW, M/S and PRM LEDs of the master unit are off (the master unit setting is
proper) in the system configuration shown below:




PS:
Power
supply

LED Status

CCL003Z

Master

Station

1 Station

2 Station

3

Cause Corrective

Action

L.RUN

L.RUN

L.RUN

SD

SD

SD

RD

RD

RD

L.ERR

L.ERR

L.ERR

Normal

-

L.RUN

L.RUN

L.RUN

SD

SD

SD

RD

RD

RD

TIME○

LINE○

or

TIME●

LINE○

L.ERR

L.ERR

L.ERR

Poor contact of the
CCL003Z with the
Inverter or the power
supply is not supplied.

Plug the CCL003Z
securely.
Check the connector.

L.RUN

L.RUN

L.RUN

SD

SD

SD

RD

RD

RD

L.ERR

L.ERR

L.ERR

Since the L.RUN LEDs
of station 2 and later are
off, the communication
cable between the unit 1
and 2 is open or
disconnected from the
terminal block.

Referring to the LED
"on" condition, search
for an open point and
repair.

L.RUN

L.RUN

L.RUN

SD

SD

SD

RD

RD

RD

L.ERR

L.ERR

L.ERR

The communication
cable is shorted.

Among the three wires
of the communication
cable, search for
shorted wire and
repair.

L.RUN

L.RUN

L.RUN

SD

SD

SD

RD

RD

RD

TIME●

LINE●

or

TIME○

LINE●

L.ERR

L.ERR

L.ERR

The communication
cable is wired improperly.

Check the wiring on
CCL003Z terminal
block and correct the
improper wiring point.

:

On,

○:

OFF, ◎:

Flicker,

*:

Any of on, flicker or off.

Master

CPU Unit

Station

1

Inverter

P

S

Station

2

Inverter

Station

3

Inverter