E658130

- 13 -

5.2. Communication parameters for CCL003Z

Title

Function Description

c100

Communication error detection
delay time

0.0 - 100.0 sec.

c101

Inverter operation at the
communication loss action

0: Stop and controlled by cmod, fmod
1: Operation continue
2: Deceleration stop
3: Coast stop
4: Network error stop (err8 trip)
5: Preset speed operation (by c102 setting)

c102

Preset speed
operation selection

0: None
1 to 15: Preset speed

c103

Communication time-out
condition selection

0: Disconnection detection
1: When communication mode enable (Both cmod and

fmod

are set CANopen or communication option) only

2: 1 + Driving operation

c120

*

CC-Link station number
selection

1 to 64
Set the number of stations of inverters (Remote device
station).

c121

*

CC-Link baud rate selection

0: 156kbps
1: 625kbps
2: 2.5Mbps
3: 5Mbps
4: 10Mbps
Set the baud rate for CC-LINK network

c122

*

CC-Link extended selection

0: Occupies one station (V1.10)
1: Occupies one station double (V2.0)
2: Occupies one station quadruple (V2.0)
3: Occupies one station octuple (V2.0)
The function of remote registers can be enhanced.

*

Set parameters according to the CC-Link network system.