Initial installation – Tripp Lite SNMP Solo MT-SE-37/02 User Manual

Page 15

Advertising
background image

Tripp Lite

Initial Installation

9

Initial Installation

This section describes the installation of the SNMP Solo
adapter when you connect it to the UPS and the network. (Refer
to the Configuration section for network communications’
setup.) For configuration, connect the SNMP Solo temporarily to
a PC with a terminal emulation package or to a dumb terminal.
The following steps guide you in connecting the SNMP Solo to
the network and UPS.

1. Install the UPS.
2. Adjust the DIP switches on

the SNMP Solo for
Configuration. Switch 1 is
ON when down; switch 2 is
OFF when up.

3. Temporarily, connect the SNMP Solo

adapter to a dumb terminal or to a PC with
the terminal emulation package.
a) Using the configuration cable, connect the

end of the cabled labeled “SM-SER-117A”
into a dedicated RS-232 serial port on the
configuration PC.

b) Connect the other end into the SNMP

Solo’s serial port.

4. Configure the communications settings.

a) Use the following settings to configure the dumb

terminal or PC.

Baud rate

! 9600

Flow Control Xon/XOFF

Data bits

! 8

Handshaking

! None

Stop bit

! 1

Terminal Type:

! ANSI (VT100)

Parity

! None

Local Echo

! Off