Installation of indoor unit, Requirement, Installation of ceiling panel (sold separately) – Toshiba MMU-AP0071MH User Manual

Page 11

Advertising
background image

8

Hanging bolt
(W3/8 or M10)

Nut
(W3/8 or M10)

(1) M10 washer supplied, all other material

must be procured locally.

(2) To ensure that the unit is mounted safely, the

hanging bolt must be positioned just below
the hanging bracket as shown in the diagram.

(1)
M10 flat washer
(Accessory)

(2)
M10 flat washer
(Accessory)

Nut
(W3/8 or M10)

Installation gauge

2) 10 to

42 mm

1) 23 to 28

mm

Ceiling board

Indoor unit

Installation of indoor unit

• Attach the nut (M10 or W3/8: Procured locally) and washer (Ø34 mm)

to the hanging bolt.

• Put washers at either side of the T-groove on the hanging bracket of

the indoor unit in order to hang the unit.

• Using a spirit level, check that all four sides are horizontal.

(Horizontal positioned within 5 mm)

• Cut off the installation gauge from the installation pattern.

• Using the installation gauge check and adjust clearance between the

indoor unit and the ceiling opening (1) (10 to 42 mm on each side).
Ensure that the unit is level to the ceiling and within a distance of (2)
23 mm to 28 mm below.
The installation gauge has details of how to use printed on it.

Note) Install the indoor unit so that the end part of opening does not

come into contact with the drain socket piping.

REQUIREMENT

Before installation of the indoor unit be sure to
remove the transportation cushion found between
the fan and the bell mouth.
Running the unit without removing the cushion
may damage the fan motor.

Indoor unit

Level vial (Horizontal: within 5 mm)

Hanging bolt

Hanging
metal

Installation gauge

Ceiling board

10 to 42

mm (2)

23 to 28

mm (1)

Installation of ceiling panel
(Sold separately)

Install the ceiling panel after completion of the
installation of the indoor unit, including all piping and
wiring.

Install the ceiling panel as per the supplied Installation
Manual.

Check the installation dimensions of the indoor unit
and the ceiling opening are correct and then install.

REQUIREMENT

Ensure the ceiling panel is mated to the ceiling
surface or the indoor unit.

If the panel and unit are not mated together this
may result in the formation of dew condensation
causing a possible water leak.

First remove the 4 corner caps from the ceiling
panel and fit to the indoor unit.

Be sure to remove the cushion for transportation
between the fan and the bell mouth.

Installation of remote controller (Sold separately)

For installation of the wired remote controller, follow the Installation Manual supplied with the remote controller.

• Do not expose remote controller to direct sunlight or excessive heat.

• When using a wireless type remote controller check receiver on the indoor unit receives a signal.

• For a wireless type controller ensure that it is used and mounted a minimum distance of 1m apart from any other

electrical devices (TV, Stereo, etc). As this may cause interference with the devices.