16

Cable connection

REQUIREMENT

• Be sure to locate the cable through the cable connection port of the indoor unit.

• Ensure additional wire length of approximately 100 mm at the indoor unit electric parts box.

This is to enable ease of any service work in the future.

• The low-voltage circuit is provided for the remote controller.

• Remove the cover of the electric parts box by removing the mounting screws (3 off) and push the hooking section.

(The cover of the electric parts box remains hanged to the hinge.)

• Tighten the screws on the terminal block and secure the cables with cord clamp fitted to the electric parts box.

(Do not apply tension to the connecting section of the terminal block.)

• Using the supplied thermal insulation for the sealing of the cable connecting port, seal the cable connecting port.

(Otherwise dew condensation may be caused.)

• Mount the cover of the electric parts box ensuring the cables are not pinched.

(Mount the cover after the ceiling panel has been wired to the electric box.)

P.C. board

Cover of electric parts box

Hooking section

Screw

Screws

Electric parts box

Thermal insulation to cabling connecting port

R

(L)

S

(N)

10

10

50

70

Earth line

Connecting
cord

R(L) S(N)

Cord clamp

Heat insulator B

Heat insulator A

Indoor/Outdoor
inter-unit cable/
Remote controller
terminal block

Power supply
terminal block

U

1

U

2

A B

Adhered surface

Notched section