Connection of drain pipe, Requirement, Drain up – Toshiba MMU-AP0071MH User Manual

Page 13: Check the draining

Advertising
background image

10

Connection of drain pipe

• Connect the hard socket (Procured locally) to the

hard socket side of the supplied flexible hose which
has been installed.

• Connect the drain pipes (Procured locally) in turn to

the connected hard sockets.

REQUIREMENT

• Using a adhesive agent for vinyl chloride,

connect the hard vinyl chloride pipes so that
water does not leak.

• Allow sufficient time for the adhesive to set and

harden. (Refer to the instructions of the
adhesive.)

Drain up

When it is not possible to achieve a natural downward
slope on the drain pipe, you can create a vertical lift
(Drain up) on the pipe.

• Set the height of the drain pipe within 850 mm from

the bottom surface of the ceiling.

• The drain pipe should be piped from the drain pipe

connecting port horizontally for a maximum of
300 mm and then piped vertically.

• After piping the vertical lift, ensure the pipework is

set to a downward gradient.

Check the draining

After completion of drain piping,

Check water drains away and that no water leaks from
any of the connecting parts. At the same time check
for any abnormal sounds from the drain pump.

Ensure drainage is checked during cooling mode.

When the electric work has finished:

• Before installing the ceiling panel, pour water as

shown in the following figure, check water drains
from the drain pipe connecting port (Transparent) in
COOL mode and then check there are no water
leaks from the drain pipes.

When the electric work has not finished:

• Pull out the float switch connector (3P: Red) from

P.C. board connector (CN34: Red) of the electric
parts box. (Ensure the power is turned off.)

• Connect the single-phase 220-240V, 1N, 50Hz (or

220V, 1N, 60Hz) power to the terminal blocks R (L)
and S (N). (Never apply 220-240V to (A), (B), (U1)
and (U2).)

• Pour water referring to the figure.

(Amount: 1500 cc to 2000 cc)

• When the power is turned on, the drain pump motor

drives automatically. Check water is drained from
the drain pipe connecting port (Transparent), and
then check there is no water leak from the drain
pipes.

• After checking for water leaks on the drain, turn off

the power supply, and re-attach the float switch
connector to the original position (CN34) on the P.C.
board and refit the electric parts box.

Rising up

627.5mm or less

Rising up 850mm or less

300mm
or less

Indoor unit

Underneath of ceiling

220–240V, 1N

~

, 50Hz

220V 1N

~

, 60Hz

White

Black

CN34
(RED)

Black

Red

Pull out connector CN34 (Red) from P.C. board.

R(L)

S(N)