Check method

On the remote controller (Main remote controller, Central control remote controller) and the interface P.C. board of
the outdoor unit, a check display LCD (Remote controller) or 7-segment display (on the outdoor interface P.C.
board) operation is provided. Therefore the operation status can be known. Using this self-diagnosis function, a fault
and the location of this fault within the air conditioning system can be located, as shown in the table below.

Check code list

The following list shows each check code. Find the check contents from the list according to part to be checked.
• In case of a fault from the indoor remote controller: See “Main remote controller display” in the list.
• In case of a fault from the outdoor unit: See “Outdoor 7-segment display” in the list.
• In case of a fault from the indoor unit with a wireless remote controller:

See “Sensor block display of receiving unit” in the list.

Terminology

AI-NET : Artificial Intelligence.
IPDU : Intelligent Power Drive Unit

¡

: Lighting,

¤

: Flashing,

l

: Goes off

ALT. : Flashing is alternately when there are two flashing LED.
SIM : Simultaneous flashing when there are two flashing LED.

Check code

Wireless remote controller

Outdoor 7-segment display

Sensor block display

of receiving unit

Main

remote

controller

display

Auxiliary code

AI-NET central

control display

Operation

Timer Ready Flash

Check code name

Judging device

E01

¤

l l

Communication error between indoor and remote
controller (Detected at remote controller side)

Remote controller

E02

¤

l l

Remote controller transmission error

Remote controller

E03

97

¤

l l

Communication error between indoor and remote
controller (Detected at indoor side)

Indoor

E04

04

l

l

¤

Communication circuit error between indoor/outdoor
(Detected at indoor side)

Indoor

E06

E06

No. of indoor units in which
sensor has been normally
received

04

l

l

¤

Decrease of No. of indoor units

I/F

E07

l

l

¤

Communication circuit error between indoor/outdoor
(Detected at outdoor side)

I/F

E08

E08 Duplicated indoor addresses

96

¤

l l

Duplicated indoor addresses

Indoor / I/F

E09

99

¤

l l

Duplicated main remote controllers

Remote controller

E10

CF

¤

l l

Communication error between indoor MCU

Indoor

E12

E12

01: Indoor/Outdoor

communication

02: Communication between

outdoor units

42

¤

l l

Automatic address start error

I/F

E15

E15

42

l

l

¤

Indoor is nothing during automatic addressing

I/F

E16

E16

00: Capacity over

01 ~: No. of connected units

89

l

l

¤

Capacity over / No. of connected indoor units

I/F

E18

97, 99

¤

l l

Communication error between indoor units

Indoor

E19

E19

00: Header is nothing

02: Two or more header units

96

l

l

¤

Outdoor header units quantity error

I/F

E20

E20

01: Outdoor of other line

connected

02: Indoor of other line

connected

42

l

l

¤

Other line connected during automatic address

I/F

E23

E23

15

l

l

¤

Sending error in communication between outdoor units

I/F

E25

E25

15

l

l

¤

Duplicated follower outdoor addresses

I/F

E26

E26

No. of outdoor units which
received signal normally

15

l

l

¤

Decrease of No. of connected outdoor units

I/F

E28

E28 Detected outdoor unit number

d2

l

l

¤

Follower outdoor unit error

I/F

E31

E31

01: IPDU1 error
02: IPDU2 error

03: IPDU1, 2 error

04: Fan IPDU error

05: IPDU + Fan IPDU error

06: IPDU2 + Fan IPDU error

07: All IPDU error

CF

l

l

¤

IPDU communication error

I/F