Toshiba MMU-AP0071MH User Manual

Page 25

Advertising
background image

22

In case of wireless remote controller

Receiver unit

M4 × 25 screw
(2 pieces)

Small screw

Spacer

Notch

Nameplate

N
E

Procedure

1

2

3

4

Description

Remove a small screw which fixes the nameplate of the receiver unit.

Remove the nameplate of the sensor section by inserting a minus screwdriver, etc into the notch at the bottom
of the plate, and set the Dip switch to [TEST RUN ON].

Execute a test operation with

button on the wireless remote controller.

,

, and

LED flash during test operation.

• Under status of [TEST RUN ON], the temperature adjustment from the wireless remote controller is invalid.

Do not use this method in the operation other than test operation because the equipment is damaged.

Use either COOL or HEAT operation mode for a test operation.

* The outdoor unit does not operate approx. 3 minutes after power-ON and operation stop.

After the test operation finished, stop the air conditioner from the wireless remote controller, and return Dip
switch of the receiver section as before.
(A 60-minutes timer clearing function is attached to the receiver section in order to prevent a continuous test
operation.)

Advertising