DRAIN PIPING WORK

REQUIREMENT

• Ensure insulating of the drain pipes and connecting parts on the indoor units.

• The drain pipe should have a downward slope of at least 1/100 and ensure

there are no swells or blockages as this will cause abnormal sounds.

• The maximum traverse length of drain pipe is 20 m. Provide support

brackets at intervals of 1.5 to 2 m where necessary to prevent movement.

• Install the combined piping as shown in the illustration.

• Do not create an air purge in the pipework,

as the water would leak from this point.

• The hard vinyl-chloride pipe cannot be connected

directly to the drain pipe connecting port of the indoor unit.
For connection with the drain pipe connecting port,
ensure that the supplied flexible hose is fitted.

• Adhesive agent cannot be used for the pipe

connecting port (hard socket) on the indoor unit.

Be sure to use the supplied hose band for fixing,
otherwise there is a risk of damage or water
leakage from the drain pipe connecting port.

CAUTION

• Install the drain piping so that the water

drains effectively.

• Apply heat insulation to prevent dew

condensation from forming.

• Incorrectly installed pipework may result

in a water leak.

Pipe material/Insulator and size

The following materials for piping work and insulation
are to be procured locally.

Trap

Arched
shape

Support
bracket

1/100 or more
downward

Heat
insulator

1.5m to 2m

NO

GOOD

As long as possible (10cm)

VP30 or more

Downward slope
1/100 or more

VP25

VP25

VP25

(Collective pipes)

Connection of flexible hose

• Insert the soft socket of the supplied flexible hose

into the connecting port of the drain pipe.

• Align the supplied hose band to the pipe connecting

port end, and tighten.

REQUIREMENT

• Fix the soft socket with the supplied hose

band, tighten at the upper position of the
unit.

• The supplied flexible hose can bend up to

a maximum of 45°

Attached hose band Attached flexible hose

Drain pipe connecting port
(Hard socket)

VP25 vinyl chloride pipe
(Procured locally)

Adhesive agent prohibited

Soft socket

Hard socket

Socket for VP25
(Procured locally)

Riser (Trap)

90˚ Bend

max

45˚

max

45˚

OK

NO GOOD

Socket for VP25 vinyl chloride pipe
(To be local procure)

Align the attached hose band to the
end of hose, set the tightening
position upward, and then tighten it.

Indoor unit body

Drain pipe
connecting port
(Transparent)

Flexible hose
(Accessory)

VP25 vinyl chloride pipe
(To be local procure)

Pipe material

Insulator

Hard vinyl chloride pipe socket for VP25

Hard vinyl chloride pipe VP25
(Outer diameter Ø32 mm)

Foamed polyethylene foam, thickness:
10 mm or more