Troubleshooting – Toshiba MMU-AP0071MH User Manual

Page 28

Advertising
background image

25

9

TROUBLESHOOTING

Check code

Wireless remote controller

Outdoor 7-segment display

Sensor block display

of receiving unit

Main

remote

controller

display

Auxiliary code

AI-NET central

control display

Operation

Timer Ready Flash

Check code name

Judging device

F01

0F

¤ ¤

l

ALT

Indoor TCJ sensor error

Indoor

F02

0d

¤ ¤

l

ALT

Indoor TC2 sensor error

Indoor

F03

93

¤ ¤

l

ALT

Indoor TC1 sensor error

Indoor

F04

F04

19

¤ ¤

¡

ALT

TD1 sensor error

I/F

F05

F05

A1

¤ ¤

¡

ALT

TD2 sensor error

I/F

F06

F06

18

¤ ¤

¡

ALT

TE1 sensor error

I/F

F07

F07

18

¤ ¤

¡

ALT

TL sensor error

I/F

F08

F08

1b

¤ ¤

¡

ALT

TO sensor error

I/F

F10

OC

¤ ¤

l

ALT

Indoor TA sensor error

Indoor

F12

F12

A2

¤ ¤

¡

ALT

TS1 sensor error

I/F

F13

F13

01: Comp. 1 side
02: Comp. 2 side

43

¤ ¤

¡

ALT

TH sensor error

IPDU

F15

F15

18

¤ ¤

¡

ALT

Outdoor temp. sensor miscabling (TE, TL)

I/F

F16

F16

43

¤ ¤

¡

ALT

Outdoor pressure sensor miscabling (Pd, Ps)

I/F

F23

F23

43

¤ ¤

¡

ALT

Ps sensor error

I/F

F24

F24

43

¤ ¤

¡

ALT

Pd sensor error

I/F

F29

12

¤ ¤

l

SIM

Indoor other error

Indoor

F31

F31

1C

¤ ¤

¡

SIM

Indoor EEPROM error

I/F

H01

H01

01: Comp. 1 side
02: Comp. 2 side

IF

l

¤

l

Compressor break down

IPDU

H02

H02

01: Comp. 1 side
02: Comp. 2 side

1d

l

¤

l

Magnet switch error
Overcurrent relay operation
Compressor trouble (lock)

MG-SW

Overcurrent relay

IPDU

H03

H03

01: Comp. 1 side
02: Comp. 2 side

17

l

¤

l

Current detect circuit system error

IPDU

H04

H04

44

l

¤

l

Comp 1 case thermo operation

I/F

H06

H06

20

l

¤

l

Low pressure protective operation

I/F

H07

H07

d7

l

¤

l

Oil level down detective protection

I/F

H08

H08

01: TK1 sensor error
02: TK2 sensor error
03: TK3 sensor error
04: TK4 sensor error

d4

l

¤

l

Oil level detective temp sensor error

I/F

H14

H14

44

l

¤

l

Comp 2 case thermo operation

I/F

H16

H16

01: TK1 oil circuit system error
02: TK2 oil circuit system error
03: TK3 oil circuit system error
04: TK4 oil circuit system error

d7

l

¤

l

Oil level detective circuit error
Magnet switch error
Overcurrent relay operation

I/F

MG-SW

Overcurrent relay

L03

96

¤

l

¤

SIM

Indoor center unit duplicated

Indoor

L04

L04

96

¤

¡

¤

SIM

Outdoor line address duplicated

I/F

L05

96

¤

l

¤

SIM

Duplicated indoor units with priority
(Displayed in indoor unit with priority)

I/F

L06

L06 No. of indoor units with priority

96

¤

l

¤

SIM

Duplicated indoor units with priority
(Displayed in unit other than indoor unit with priority)

I/F

L07

99

¤

l

¤

SIM

Group line in individual indoor unit

Indoor

L08

L08

99

¤

l

¤

SIM

Indoor group/Address unset

Indoor, I/F

L09

46

¤

l

¤

SIM

Indoor capacity unset

Indoor

L10

L10

88

¤

¡

¤

SIM

Outdoor capacity unset

I/F

L20

L20

98

¤

¡

¤

SIM

Duplicated central control addresses

AI-NET, Indoor

L28

L28

46

¤

¡

¤

SIM

Over No. of connected outdoor units

I/F

L29

L29

01: IPDU1 error
02: IPDU2 error
03: IPDU3 error
04: Fan IPDU error
05: IPDU1 + Fan IPDU error
06: IPDU2 + Fan IPDU error
07: All IPDU error

CF

¤

¡

¤

SIM

No. of IPDU error

I/F

L30

L30 Detected indoor address

b6

¤

¡

¤

SIM

Indoor outside interlock

Indoor

L31

Extended I/C error

I/F

Advertising