Wiring the Inverter

3–2

975-0320-01-01

The ground bar accepts wires up to #4 AWG. Torque ground wires as specified in
Table 3-1.

Figure 3-1 Ground Conductor Knockouts

Knockouts for ground conductors

Ground bar

Table 3-1 Torque Values for Ground Wiring

Wire Size

Torque Value

AWG

mm

2

in-lb

Nm

14–10

2.5–6.0

25–35

3.0–4.0

8

10

30–40

3.4–4.5

6–4

16–25

35–45

4.0–5.0

Important:

In most models, the negative PV conductor is internally bonded to the

ground system within the inverter’s ground fault detection circuit. Inverter models marked
with the “-POS” suffix are positive grounded and have the positive PV conductor
internally bonded to the ground system through the inverter’s ground fault protection
circuit. It is important that the negative (or positive) PV conductor is not bonded to the
ground at any other point in the system.